All systems are operational

Past Incidents

Saturday 3rd November 2018

No incidents reported

Friday 2nd November 2018

Partial Power Outage

We are encountering a power outage in rack 05 in SmartDC datacenter. This power outage might result in unavailability of your services.

Our data center engineers are on-site to investigate the cause of this issue. Please be assured that we will do our utmost best to keep the downtime as short as possible.

Update: As of 10.32 the outage has been fixed, we're investigating the cause of this incident. Update: There was a short outage of 11:19 - 11:20 Update: as of 11:10 OUr engineers are using thermal cameras to check if there is a hardware failure in the rack. Update 2nd November 2018 13:58 CET: During investigating we have noticed a new power outage in Rack 5 started at 2nd November 2018 10:28 - 10:32 CET. Unfortunately, we couldn't find the faulty hardware as easy as in Rack 1. After this second outage in Rack 5, our engineers on-site decided to divide the servers of Rack 5 into two separate groups to eliminate possible hardware and other causes which can lead to power outages.

Again we checked if we exceeded our maximum power consumption of 25 Ampere in this group, but this was not the case. Our engineers started to use thermal cameras to find possible hardware failures but nothing unusual was measured. We are still investigating this issue and new power outages might happen again. Our power supplier reported that there might be issues on the circuit breaker. To eliminate this possible issue they have to switch the power from rack 5 to another power source.

Once we have more information we will keep you updated.


Incident start: 02/11/2018 10:28 CET Incident end: 02/11/2018 10:32 CET Impact: Rackswitches and servers in 05 are down

Thursday 1st November 2018

Network Partial power outage

We are encountering a power outage in rack 01 and rack 05 in SmartDC datacenter. This power outage might result in unavailability of your services.

Our data center engineers are on-site to investigate the cause of this issue. Please be assured that we will do our utmost best to keep the downtime as short as possible.

Update: As of 23:39 the outage has been fixed, we're investigating the cause of this incident. Update 2nd November 2018 13:56 CET: On the 1st of November 2018 around 22:30 CET we experienced a partial power outage in Rack 1. This incident was resolved around 23:39.

Reason of outage: The circuit breaker of the group tripped. We checked maximum power consumption, it didn't exceed 25A. To eliminate hardware failures in Rack 1 we started the servers 1 by 1. During this procedure we found a server whith a faulty power supply. We replaced the server with a new once and all servers are up and running in this rack. During the recovery of the power outage of Rack 1 we experienced a similar situation in Rack 5 which started at 23:31 and was resolved 23:40 CET.

Incident start: 01/11/2018 22:34 CET Incident end: 01/11/2018 23:39 CET Impact: Rackswitches and servers in racks 01 and 05 are down

Wednesday 31st October 2018

No incidents reported

Tuesday 30th October 2018

No incidents reported

Monday 29th October 2018

No incidents reported

Sunday 28th October 2018

No incidents reported